ProjectsData-centre condensers
Case study · Data centre · Vietnam · 2025

Assessing the condenser layout of a data-centre cooling system

64.4 → 53.5 °C
highest condenser inlet air temperature
48.9 → 46.0 °C
mean inlet air temperature of the 56 condensers
41.1 °C
design outdoor temperature — 1 pm in summer, 100% load
45° ↓ → 45° ↑
louver angle; blade pitch 17.2 → 25.8 cm

Context & problem

The condensers sit on three tiers behind a louver wall, close to the neighbouring building and the generator room. At the hottest hour of summer the outdoor air is already 41.1 °C, while the maker's maximum operating temperature for these models is 40–48 °C. Hot air drawn back into the condensers pushes them outside that range.

Approach

  • 3D model of the building, the neighbouring building, the louver wall, cable trays, generator room and stack, from the drawings and site survey measurements.
  • The harshest case: 1 pm in summer, 41.1 °C, west wind at 1.5 m/s (surveyed on 30/06/2025), solar radiation of 1,283 W/m² for the site coordinates; all condensers, fans and the generator at 100% load (exhaust at 519 °C, 385 m³/min).
  • Each condenser is a heat source with a fan from the catalogue (94–154 kW, 28,000–31,600 m³/h); the inlet air temperature of every unit is checked against the maker's maximum.
  • Design 1: louvers turned upward at 45°, blade pitch widened from 17.2 to 25.8 cm, generator stack redirected.

Results

  • Original design: the downward louvers hold part of the air leaving the tier-1 condensers and turn it back into the inlets; highest inlet temperature 64.4 °C, 32 of 56 condensers above the maximum operating temperature. The tier-3 condensers are hardly affected.
  • The generator exhaust makes a zone above 100 °C around the stack, at a height and location that affects neither people nor the condensers.
  • Design 1: the warm air rises along the louvers and recirculation at the inlets drops clearly; highest inlet temperature 53.5 °C, mean 48.9 → 46.0 °C, units above the limit 32 → 30.
  • The remaining exceedances come from the harsh design case (41.1 °C, peak radiation, 100% load) and from the west wind carrying one unit's hot air into its neighbour's inlet — the basis for the next optimization step.

Value

Changing the louver angle and pitch is a small structural change, yet it lowers the highest condenser inlet air temperature by almost 11 °C. The per-unit table of inlet temperatures shows exactly which positions still require improvement.

Project gallery

Inlet air temperature of the 56 running condensers, original design (grey) and design 1 (blue), against the maker's maximum operating temperature
/image/thiet-bi-trung-tam-du-lieu-02.jpg4:3 ratio (landscape)
3D model: building, three-tier condenser yard behind the louver wall, generator room and neighbouring building
/image/thiet-bi-trung-tam-du-lieu-03.jpg4:3 ratio (landscape)
Warm-air volume around the condenser yard at 1 pm in summer, full load — original design and design 1
/image/thiet-bi-trung-tam-du-lieu-05.jpg4:3 ratio (landscape)
Original design against design 1: highest inlet temperature 64.4 → 53.5 °C, mean 48.9 → 46.0 °C, units above the limit 32 → 30
/image/thiet-bi-trung-tam-du-lieu-06.jpg4:3 ratio (landscape)

Fitting condensers into a tight space?

Check recirculation and the inlet temperature of every unit on the hottest day of the year, before finalizing the louvers and unit positions.

Send project details

Related projects: Blast freezer · HVAC & thermal capability · HVAC & Buildings